Skip to main content

Energy Balance in Class II Biosafety Cabinets

Increasing the energy-efficiency of class II biosafety cabinets is an important step to reducing overall energy use (and energy cost) in labs.

Biosafety cabinets require a relatively high amount of energy to run, because they require airflow to maintain containment and protection, and they are typically operated continuously to preserve aseptic conditions. Biosafety cabinets also impact the energy requirements of a facility’s HVAC system, which contributes the high energy consumption. To determine the total energy consumption of a biosafety cabinet, both the plug load of the cabinet and the energy used by the HVAC system must be calculated.

The most common types of class II biosafety cabinets are Type A2 and Type B2, and they vary in energy requirements because of how they operate. In addition to a risk assessment, it is important to consider all your laboratory’s heating, cooling and air change requirements when selecting the appropriate type of biosafety cabinet.

How to Calculate the Energy Consumption of a Biosafety Cabinet

Calculating Biosafety Cabinet Plug Load Energy Cost

The electrical energy required to run a biosafety cabinet is referred to as plug load. Plug load is measured in watts (W) and is calculated by multiplying voltage (V) by operating amperage (A). The cost of cabinet power is simply the total watts necessary to run the unit (V x A) converted to kilowatt hours (kWh) per year (W / 1000 × 24 hours × 365 days). Using the local kWh electricity rate, you can calculate the total cost to power the unit and easily compare different types of class II biosafety cabinets.

Exhaust and Supply Airflow

The amount of air supplied to the lab in order to replace the air exhausted and cool the space due to heat loading is calculated by determining the amount of flow (CFM) required, and then determining the annual cost using your facility’s average cost per CFM.

Either the biosafety cabinet exhaust, the laboratory cooling load or the air change requirement will determine the amount of supply air required (and therefore, the cost associated with conditioning the air). If the laboratory flow rate is driven by the cabinet’s exhaust requirement, then the cooling load will most likely be satisfied. If the laboratory is heat load driven, the cost of the biosafety cabinet exhaust should be included in the cost of the exhaust used to cool the space. The amount of energy associated with the conditioned supply air is about the same whether it is used to satisfy the cabinet’s heat contribution to the laboratory or to satisfy the cabinet’s intake / exhaust requirement.

Comparing Energy Balance in Type A2 and Type B2 Biosafety Cabinets

The below chart is a representation of how these energy requirements (plug load, exhaust system energy, and cabinet exhaust airflow for biosafety cabinet exhaust and heating load) add up to total operating cost for each type of biosafety cabinet. The exact cost will vary depending on local electricity rates, climate, code requirements and what is driving the air changes in a particular laboratory, so the is for comparison purposes only.

The chart shows that a recirculating cabinet exhausted to the room (Type A2) contributes the most to the laboratory cooling load, but there is no increase to the exhaust system power because all the air is exhausted to the room. In contrast, a total exhaust cabinet (Type B2) contributes an insignificant amount to the laboratory cooling load, but it contributes significantly to the exhaust system power because 100% of the air is exhausted.

You may expect that venting a cabinet outdoors is more expensive than venting to the room, however this analysis does not show this. It is actually less costly to operate a Type A2 cabinet vented to the outdoors because the heat load associated with venting to the room is significant. When vented through a canopy connection to the exhaust system, heat is captured and released through the exhaust system, which reduces the cabinet’s heat load to the laboratory. Therefore, even if a risk assessment determines that the Type A2 cabinet can be exhausted to the room, it may be more energy-efficient to vent outside.

Energy-Efficient Biosafety Cabinets from Baker

Here at Baker, we’re committed to offering the safest, best performing products for you and your work, while also developing technologies to increase efficiency. Our SterilGARD e3 Type A2 cabinet and BioChemGARD e3 Type B2 cabinet are the most energy-efficient in the industry.

Download our BioChemGARD e3 white paper to see how the BioChemGARD can reduce your operating costs by 49% in operational costs.

You May Also Be Interested In:

BSC Technical Training | Baker Company | Oct 19-21, 2026

Read more about BSC Technical Training | <span translate='no'>Baker</span> Company | Oct 19-21, 2026

Baker Flow Werkbanken – Kwaliteit die blijft presteren

Read more about <span translate='no'>Baker</span> Flow Werkbanken – Kwaliteit die blijft presteren

Baker Hosts International Dealer Meeting & Factory Visit in Bridgend, Wales

Read more about <span translate='no'>Baker</span> Hosts International Dealer Meeting &amp; Factory Visit in Bridgend, Wales

First EuroFlow EF-N Installed in the U.S. at University of Miami Sylvester Comprehensive Cancer Center

Read more about First EuroFlow EF-N Installed in the U.S. at University of Miami Sylvester Comprehensive Cancer Center

Cold Lab Services and The Baker Company: A Strong New Partnership

Read more about Cold Lab Services and The <span translate='no'>Baker</span> Company: A Strong New Partnership

Lifecycle Support Update 2026: Baker and/or CleanAir Benelux Flowbenches

Read more about Lifecycle Support Update 2026: <span translate='no'>Baker</span> and/or CleanAir Benelux Flowbenches

The Baker Company certified ISO 14001:2015 for 2026

Read more about The <span translate='no'>Baker</span> Company certified ISO 14001:2015 for 2026

How Hypoxia Rewires Epigenetics and Splicing to Drive EMT in Breast Cancer

Read more about How Hypoxia Rewires Epigenetics and Splicing to Drive EMT in Breast Cancer

What Oxygen Really Means for Extracellular Vesicles

Read more about What Oxygen Really Means for Extracellular Vesicles

Stay up to date